Power: 110-220Vac±10%, 50 / 60Hz (or DC12V / DC24V)
● The temperature range of measurement and control: -50 ℃ ~+110 ℃
● Resolution: 0.1
● Accuracy:±1 ℃
● Relay output contact capacity: Heating: 10A/240VAC, Refrigeration: 10A/240VCA
● Sensor H type: imported NTC sensor, 1 meter long line
● Shell material: gray ABS flame retardant plastic shell
● Net weight 120g hair weight 140gPressSet 5You can enter the internal parameter settings in seconds, press up and downSwitchP0...P8according toRstConfirm the return
Code | Code description | Scope | Factory setting |
P0 | Refrigeration mode/Heating mode | C/H | C |
P1 | Back settings | 0.1-30 | 2 |
P2 | Maximum setting range | 120 | 120 |
P3 | Minimum setting range | -55 | -55 |
P4 | Temperature correction | -10.0~+10.0Spend | 0 |
P5 | Delay starting time | 0-10minute | 0 |
P6 | High temperature alarm | -50~110 | off |
P7 | Data lock switch | on/off | off |
P8 | reset | on/off | off |
P0Refrigeration, heating mode
The high temperature startup is the refrigeration mode, please set it toC
The low temperature startup is the heating mode, please set it toH
P1Back settings
Heating mode (H) Below: Measurement value ≤ set value -Start the output heating to the set value to stop at the time of return.
Refrigeration mode (C) Below: Measurement value ≥ set value + Return output refrigeration to the set value stop
P2Maximum setting range: The highest value does not exceed this value when setting temperature
P3Minimum setting range: The minimum value when setting temperature is not less than this value
P4Temperature correction
When the measurement temperature and standard temperature are deviated, you can use this function to correct it. The temperature after correction=Correctional temperature+Correction
P5Delay starting timeUnit: minute
When the compressor equipment is refrigerated, the delay time can be set according to the need. When the controller outputs the device will not start immediately, it needs to be started after the setting is completed
P6High temperature alarm
When the measurement value is greater than this value screen display---And Didi sounds alarm, while forcibly disconnect the output
P7Data lock function
To turn on the data lock, you can keep the current settings from being changed. At this time, the setting temperature and function are invalid. If you need to modify it, you need to turn off the data lock function
P8reset
PressSETSwitchP8, Press onceSETSet ason,according toRstreset
You can also hold down the + -key without letting go of the self -inspection and restoration of the factory setting
Fourth, use instructions
Please connect the power supply according to the parameter and the line diagram, and connect the refrigeration or heating equipment on the output end
Select heating (enterP0chooseH) Or cooling (enterP0chooseC)model
Set the temperature method: press onceSetThe screen flickered, press the temperature to be set up and down, pressRstConfirm the return
PanelOUTIndications: Flinting indicates the delay of cooling or heating start, Chang Liang means output
Digital tube: displayLLLOpen the way for the sensor; displayHHHIn order to exceed the measurement range temperature controller, power off will be forced; display---Call alarm for high temperature